Process Details

Description
Sprinkler System Inspection
Folder Number
25 113110 00 FI
Folder Details
1288 HAWTHORNE AVENUE NE
Permit Type
Fire System Permit - Commercial - Fire Sprinkler
Scheduled Date
8/7/2025
Assigned Staff
Deputy Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 8/7/2025 Sara Roth Inspected 1. Cover inspection 1st floor - Okay to cover 2. Dry system (porte cochere) hydro passed @ 235 psi. 3. Wet system hydro passed @ 220 psi. 4. Need to do 24hr air pressure test. 5. As-builts for minor changes, marked on plans (1st floor inspection only)