Process Details

Description
Fire Comments
Folder Number
24 113646 00 PLN
Folder Details
383 FARM CREDIT DRIVE SE
Permit Type
Planning - Type II
Scheduled Date
11/15/2024
Completed Date
12/2/2024
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 12/2/2024 Sean Mansfield Complete fire department access (including aerial) is required. fire hydrant is required within 600 feet of all portions of the buildings and 100 feet of the FDCs as measured along an approved route.