Process Details

Description
Sprinkler System Inspection
Folder Number
24 111049 00 FI
Folder Details
5775 COMMERCIAL STREET SE
Permit Type
Fire System Permit - Commercial - Fire Sprinkler
Scheduled Date
6/2/2025
Assigned Staff
Deputy Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 10/28/2024 Justin Guinan Inspected 2nd and 3rd floor ok for cover, minus the south stairwell sidewall and the elevator heads. As builts for omitted and added heads.
2 11/5/2024 Janet Campbell Inspected 1st floor main hydro passed 4th floor hydro passed 4th floor ok for cover, minus the corridor, south stairwell sidewall, and the elevator heads. As builts for omitted and added heads.
3 11/18/2024 PAC Portal Cancel Inspection Request Cancelled by PACPORTAL ([email protected])
4 11/19/2024 Janet Campbell Inspected 1st floor hydro passed for the branch lines and the residential side 1st floor cover ok, minus the corridor, commercial side bathrooms, stairwell, and elevator. As builts for omitted and added heads
5 5/6/2025 Sara Roth Inspected 1. Hydro of entire standpipe - Passed @ 220 psi. 2. Cover inspection of corridors on 1st, 2nd, and 3rd floors - okay for cover. 3. Cover of head in office bathroom on 1st floor, one head on second floor near library, and one head in southeast unit on 4th floor. 4. Unable to mark covered area on plans. Need approved as built drawings on site for cover inspections due to all the changes made. 5. Unable to cover 4th floor corridor due to the ceiling being masked off.
6 6/2/2025 Sara Roth Inspected Cover inspection of corridor on 4th floor. Reinspected corridors on floors 1-3 with asbuilts.