Process Details
- Description
- Sprinkler System Inspection
- Folder Number
- 24 105835 00 FI
- Folder Details
- 1010 HAWTHORNE AVENUE SE Suite 140
- Permit Type
- Fire System Permit - Commercial - Fire Sprinkler
- Scheduled Date
- 7/12/2024
- Completed Date
- 11/18/2024
- Assigned Staff
- Deputy Fire Marshal
Process Comments
Comment Number | Scheduled Date | Comment Date | Staff | Result | Comment |
---|---|---|---|---|---|
1 | 3/26/2024 | Janet Campbell | Inspected | Wet system NOT hydro tested Dry system passed 2 hour wet hydro. Still needs to have 24 hour air test at 40 psi | |
2 | 5/22/2024 | Janet Campbell | Inspected | **Revised dry system is now an antifreeze system. Revisions have been submitted and approved. Hydro passed on March 26, 2024 for the antifreeze system **Wet system hydro passed from working pressure and no leaks were visible at time of inspection. **Still need to set the whips & t-bars. Call in for cover inspection. | |
3 | 7/12/2024 | Justin Guinan | Inspected | Drop ceiling ok to cover. | |
4 | 11/18/2024 | Justin Guinan | Approved |