Description
Fire Alarm Inspection
Folder Number
24 106519 00 FI
Folder Details
3575 DEL WEBB AVENUE NE
Permit Type
Fire System Permit - Commercial - Fire Alarm
Scheduled Date
8/2/2024
Completed Date
8/5/2024
Assigned Staff
Deputy Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 8/1/2024 Sara Roth Corrections Did not install per plans. Devices not in code approved locations. FACP was moved and rooms changed; new devices were added. Did not perform the acceptance testing. 1. Submit as-builts for review of changes made. 2. Need approved revised plans on site for doc box. 3. Relocate devices in the office corridor.
2 8/2/2024 Sara Roth Inspected Witnessed acceptance testing - Passed. 1. Cannot approve until as-builts are approved. 2. Need approved revised plans and ROC in doc box. 3. Need notification device in the north corridor relocated to withing 15' of the exit. 4. Candela in southwest classroom was adjusted at time of testing. 5. Record of Completion to The Compliance Engine
3 8/5/2024 Sara Roth Approved Temp C/O until... 1. Approved revised plans and Record of Completion in the Document Box. 2. Record of Completion submitted to The Compliance Engine.