Process Details
- Description
- Final Fire Inspection
- Folder Number
- 22 117107 00 BP
- Folder Details
- 2920 COMMERCIAL STREET SE
- Permit Type
- Building Permit - Commercial
- Scheduled Date
- 6/20/2023
- Completed Date
- 5/19/2023
- Assigned Staff
- Deputy Fire Marshal
Process Comments
Comment Number | Scheduled Date | Comment Date | Staff | Result | Comment |
---|---|---|---|---|---|
1 | 4/28/2023 | Janet Campbell | Corrections | Please see approved plans for requirements for TCO and final inspection requirements. This may not be a complete list - but site was not ready for fire final and will call for inspection when ready. *Approved plans not on site *Exit illumination sign and egress lights are required in the break room back door *Exit and egress lights still need installed *Fire extinguishers still need mounted *Size of fire extinguishers were too small, need 2A, 10BC (5 lb) *Still need Premise ID visible and contrasting from Commercial street *Doors in fire rated corridor need to close and latch | |
2 | 5/18/2023 | Twila Pichardo | Temporary Occupancy | per Sara ok for TCO | |
3 | 5/18/2023 | Janet Campbell | Temporary Occupancy | *Replace remaining ceiling tiles *Doors in fire rated corridor need to close and latch (a couple were sticking & not latching) | |
4 | 5/19/2023 | Janet Campbell | Approved |