Process Details
- Description
- Fire Comments
- Folder Number
- 22 107794 00 RP
- Folder Details
- 5775 COMMERCIAL STREET SE
- Permit Type
- Site Plan Review - NO LONGER USED - Site Plan Review - Class 3
- Scheduled Date
- 9/7/2022
- Completed Date
- 9/13/2022
- Assigned Staff
- Fire Marshal
Process Comments
Comment Number | Scheduled Date | Comment Date | Staff | Result | Comment |
---|---|---|---|---|---|
1 | 9/13/2022 | Sean Mansfield | Complete | The Oregon Fire Code requires 2 means of fire department access which are provided from Commercial and Wiltsey. Aerial fire department access is required to be a minimum of 26' wide and located 15-30' from the structure. The building FDC shall be within 100' of a fire hydrant as measured along an approved route and in an approved location. |