Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 6/23/2022 Sean Mansfield Complete fire department access is required to be provided within 150 feet of all portions of the building. dead end fire department access over 150 feet in length will require an approved turn around. fire hydrants are required within 400 feet of all portions of the buildings (600 with an approved fire sprinkler system). fdc shall be in an approved location and within 100 feet of a fire hydrant.