Process Details

Description
Fire Comments
Folder Number
22 104269 00 RP
Folder Details
4400 BLOCK OF TURNER ROAD SE
Permit Type
Site Plan Review - NO LONGER USED - Site Plan Review - Class 3
Scheduled Date
6/17/2022
Completed Date
6/23/2022
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 6/23/2022 Sean Mansfield Complete the drive aisle around the site will need to comply with fire departments access, aerial fire department access will be required if the building height exceeds 30 feet per the Oregon fire code. fire flow will be required per OFC appendix b, and fire hydrants will be required so all portions of the building are within 600 feet (400 if not sprinkled). the fdc shall be in an approved location and within 100 feet of a fire hydrant. all measurements are made along an approved route as determined by the fire code official. the site plan provided appears to show a fire hydrant within the northern driveway.