1 |
|
4/3/2022 |
Sean Mansfield
|
Complete |
no fdc locations were provided. fire hydrant at main entrance appears to be in the drive aisle. fdc(s) shall be in an approved location and within 100' of a fire hydrant in a location that will not obstruct fire department access when hoses are deployed. fdc(s) shall clearly identified to indicate the address served. fire hydrants shall be located within 600' of all portions of the buildings as measured along an approved route. additional fire hydrant may be required at building 17 depending on fdc location to support fire fighting operations. |