Process Details

Description
Fire Comments
Folder Number
21 122676 00 RP
Folder Details
4770 LOGISTICS STREET SE
Permit Type
Site Plan Review - NO LONGER USED - Site Plan Review - Class 3
Scheduled Date
2/7/2022
Completed Date
2/7/2022
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 2/7/2022 Timothy Gorton Complete 1. FDC missing 2. Gate valves on fire line are in drive aisle. Need to be indicating. Should be PIV or remove. 3. North fire dept. access gate is less than 30 feet from public way. Need to be 30 feet or greater from Mill Creek.