Process Details
- Description
- Rough-in/Ceiling Cover Inspection
- Folder Number
- 21 108445 00 E
- Folder Details
- 990 BROADWAY STREET NE Suite 100
- Permit Type
- Electrical Permit - Commercial
- Scheduled Date
- 10/4/2021
- Completed Date
- 10/4/2021
- Assigned Staff
- Joe Hennigan
Process Comments
Comment Number | Scheduled Date | Comment Date | Staff | Result | Comment |
---|---|---|---|---|---|
1 | 8/23/2021 | Joe Hennigan | Corrections | Bulk of Tbar inspection approved, Correction status for SE cables ran in drop ceiling 110.3b Provide documentation to inspector showing cable is rated for this use- 334.12(338.10(4)). Ensure proper lighting at panel per NEC 110.26(D) | |
2 | 10/4/2021 | Joe Hennigan | Approved |