Process Details

Description
Fire Comments
Folder Number
21 101664 00 RP
Folder Details
1610 LANCASTER DR SE
Permit Type
Site Plan Review - NO LONGER USED - Site Plan Review - Class 3
Scheduled Date
5/6/2021
Completed Date
5/6/2021
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 5/6/2021 Sean Mansfield Complete Fire department access is provided from 40th and the building address will need to reflect that. The building FDC needs to be located within 100 feet of a fire hydrant and the hose lay shall not obstruct aerial access. If the building height exceeds 30 feet as measured by the OFC, then aerial fire department access will be required. Note: the provided plans indicate 2017 Oregon Residential Specialty Code. Verify with B&S if this is the correct code reference.