Process Details

Description
Fire Comments
Folder Number
21 103682 00 LD
Folder Details
4400 BLOCK BATTLE CREEK ROAD SE
Permit Type
Land Division - NO LONGER USED - Subdivision - Phased
Scheduled Date
5/6/2021
Completed Date
5/5/2021
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 5/5/2021 Sean Mansfield Complete Fire department access is required to be provided within 150 feet of all portions of the buildings. Fire hydrants are required to be located within 600 feet of all portions of the buildings. Dead end roads exceeding 150 feet in fire department access need an approved turn around. Two approved means of fire department access are required when over 30 dwelling units are provided.