Comment Number Scheduled Date Comment Date Staff Result Comment
1 10/19/2021 Sara Roth Inspected Cover Okay
2 10/19/2021 Sara Roth Corrections Hydro failed first test 215-212. Tested again and lost another 2 lbs. Total 5 lbs were lost. Retest.
3 10/20/2021 Sara Roth Inspected Hydro Passed
4 12/21/2021 Sara Roth Approved Witnessed acceptance testing - Passed. Temp C/O until. 1. CMTC submitted to TCE. 2. Heater required in riser room. 3. Finish fire caulking in riser room. 4. Riser Room sign required on door.