Process Details

Description
Fire Comments
Folder Number
20 117240 00 LD
Folder Details
255 CORDON ROAD NE
Permit Type
Land Division - NO LONGER USED - Subdivision
Scheduled Date
11/30/2020
Completed Date
11/30/2020
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 11/30/2020 Sean Mansfield Complete Two separate and approved means of fire department access are required. Fire department access is required to be provided within 150 feet of all portions of all structures. Dead end fire department access in excess of 150 feet requires an approved turnaround. Fire hydrants are required to be provided within 600 feet of all portions of the structures. All measurements are made along an approved route as determined by the fire code official.