Process Details

Description
Fire Comments
Folder Number
20 110194 00 RP
Folder Details
4629 SUNNYSIDE RD SE
Permit Type
Site Plan Review - NO LONGER USED - Site Plan Review - Class 2
Scheduled Date
10/23/2020
Completed Date
10/23/2020
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 10/23/2020 Sean Mansfield Complete Fire hydrant required within 400 feet of all portions of the structure (600 if provided with an approved fire sprinkler system). Fire department access required within 150 feet of all portions of the structure. Measurements are made along an approved route. Generator fuel tank location is determined on the size of the fuel tank.