Process Details

Description
Fire Comments
Folder Number
20 107231 00 RP
Folder Details
4072 MARKET STREET NE
Permit Type
Site Plan Review - NO LONGER USED - Site Plan Review - Class 3
Scheduled Date
7/14/2020
Completed Date
7/14/2020
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 7/14/2020 Sean Mansfield Complete Fire department access is required to be provided within 150 feet of all portions of the structures and fire department access over 150 feet requires an approved fire department turnaround. The apartments will require an approved fire sprinkler system. The FDC is required to be located near the main entrance and shall be located within 100 feet of a fire hydrant. The hose lay shall not obstruct fire department access. All portions of the structures shall be within 600 feet of a fire hydrant. All measurements are made along an approved route.