Process Details

Description
Fire Comments
Folder Number
19 123697 00 RP
Folder Details
1965 CLAXTER RD NE
Permit Type
Site Plan Review - NO LONGER USED - Site Plan Review - Class 3
Scheduled Date
2/3/2020
Completed Date
2/3/2020
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 2/3/2020 Sean Mansfield Complete All portions of the structure are required to be within 400 feet of a fire hydrant (600 ft if provided with an approved fire sprinkler system, note: the FDC is required to be within 100 ft of a fire hydrant). All portions of the building are required to be located within 150 feet of approved fire department access. All measurements are made along an approved route. Items including fire department access and water supply will be evaluated at time of building permit plan review.