It appears a fire department turnaround is being provided on site. Fire department access is required to be located within 150 feet of all portions of the building(s) and aerial access is required if the structure exceeds 30 feet in height. No water supply was shown on the plans. Fire hydrants are required to be provided within 400 feet of all portions of the buildings (600 feet if provided with an approved fire sprinkler system). The FDC is required to be located within 100 feet of the fire hydrant and the hose lay shall not obstruct fire department access. Items including fire department access and water supply will be reviewed at time of building permit plan review. |