Process Details

Description
Fire Comments
Folder Number
19 114007 00 RP
Folder Details
4722 LIBERTY ROAD S
Permit Type
Site Plan Review - NO LONGER USED - Site Plan Review - Class 3
Scheduled Date
11/25/2019
Completed Date
11/26/2019
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 11/26/2019 Sean Mansfield Complete It appears a fire department turnaround is being provided on site. Fire department access is required to be located within 150 feet of all portions of the building(s) and aerial access is required if the structure exceeds 30 feet in height. No water supply was shown on the plans. Fire hydrants are required to be provided within 400 feet of all portions of the buildings (600 feet if provided with an approved fire sprinkler system). The FDC is required to be located within 100 feet of the fire hydrant and the hose lay shall not obstruct fire department access. Items including fire department access and water supply will be reviewed at time of building permit plan review.