Process Details
- Description
- Fire Comments
- Folder Number
- 19 107583 00 RP
- Folder Details
- 1805 22ND ST SE
- Permit Type
- Site Plan Review - NO LONGER USED - Site Plan Review - Class 3
- Scheduled Date
- 7/25/2019
- Completed Date
- 7/25/2019
- Assigned Staff
- Fire Marshal
Process Comments
Comment Number | Scheduled Date | Comment Date | Staff | Result | Comment |
---|---|---|---|---|---|
1 | 7/25/2019 | Sean Mansfield | Complete | Fire department access has been provided within the site. There was no indication of how fire department access was going to be provided from the public way to the site. No fire hydrants were shown on the plan. Fire hydrants will be required to be provided within 400 feet or all portions of the exterior of the buildings as measured along an approved route. Fire flow will be calculated at the time of building permit plan review. |