Process Details

Description
Fire Comments
Folder Number
19 107583 00 RP
Folder Details
1805 22ND ST SE
Permit Type
Site Plan Review - NO LONGER USED - Site Plan Review - Class 3
Scheduled Date
7/25/2019
Completed Date
7/25/2019
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 7/25/2019 Sean Mansfield Complete Fire department access has been provided within the site. There was no indication of how fire department access was going to be provided from the public way to the site. No fire hydrants were shown on the plan. Fire hydrants will be required to be provided within 400 feet or all portions of the exterior of the buildings as measured along an approved route. Fire flow will be calculated at the time of building permit plan review.