Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 6/24/2019 Sean Mansfield Complete Fire department access is required to be provided within 150 feet of all portions of the exterior. Aerial access is required if the structure exceeds 30 feet in height. FD access is indicated in the parking lot on the plans. Fire hydrants are required within 400 feet of all portions of the exterior of the structure (600 if fire sprinklers), and within 100 feet of the fire department connection. The hose lay from the hydrant and fdc shall not obstruct fire department access. All measurements are made along an approved route. FIRE will provide additional comments are time of building permit plan review.