Process Details

Description
Fire Comments
Folder Number
15 118610 00 LD
Folder Details
3155 RIVER RD S
Permit Type
Land Division - NO LONGER USED - Partition
Scheduled Date
10/28/2015
Completed Date
10/28/2015
Assigned Staff
Fire Marshal

Process Comments

Comment Number Scheduled Date Comment Date Staff Result Comment
1 10/28/2015 10/28/2015 Fire Marshal Complete Fire department access and fire hydrants shall meet the requirements of the Salem Fire Prevention Code (SRC-58). Current fire hydrant location does not meet the travel distance requirements (400') to the proposed building. An additional fire hydrant or alternate/approved means (such as fire sprinkler system) shall be provided as part of the building permit approval. jgs