Process Details
- Description
- Fire Comments
- Folder Number
- 15 118609 00 ZO
- Folder Details
- 3155 RIVER RD S
- Permit Type
- Zoning - NO LONGER USED - Quasi-Judicial Zone Change
- Scheduled Date
- 10/28/2015
- Completed Date
- 10/28/2015
- Assigned Staff
- Fire Marshal
Process Comments
Comment Number | Scheduled Date | Comment Date | Staff | Result | Comment |
---|---|---|---|---|---|
1 | 10/28/2015 | 10/28/2015 | Fire Marshal | Complete | Fire department access and fire hydrants shall meet the requirements of the Salem Fire Prevention Code (SRC-58). Current fire hydrant location does not meet the travel distance requirements (400') to the proposed building. An additional fire hydrant or alternate/approved means (such as fire sprinkler system) shall be provided as part of the building permit approval. jgs |