1 3/11/2022 Timothy Gorton Complete Sheet A1.01 #10: Coil Grill Rollup Door requires fire department access (BOTH north and south doors) . Opti-com or Key Box/ Key Switch. Sheet C3.0 A Post Indicator Valve will be required (next to FDC) if external access to the Fire Sprinkler Riser Room is not provided.